What is the detailed analysis status of the fault occurrence body caused by the mass flow meter measuring medium? In this series of questions, we decided to decide a few points that may occur according to the situation. Arranged as follows, let's see what points are there? Did you have the same experience?
1. Failure phenomenon of mass flow meter
Nitrogen gas of a company is transported into the high-pressure nitrogen storage tank (4.5MPa) of company B through a pipe, and the pressure of the nitrogen pipe network is about 3.7MPa. After a new DN15 mass flow meter was put into use, company B reported that the nitrogen amount was different when the amount was large. Large and large nitrogen pressure drop can not be sent to the high-pressure nitrogen storage tank, the flow and pressure can not meet the production needs of B company.
2. Analysis of the cause of the failure of the mass flowmeter
First confirm the mass flow meter pressure drop. When company B needs a large amount of nitrogen supplementation, the maximum flow rate of the mass flowmeter is 310kg/h, and the pressure drop at both ends of the flowmeter reaches 1.5MPa, which is inconsistent with the theoretically calculated pressure drop of 0.041MPa; The test results show that the inner wall of the measuring tube of the flowmeter is smooth, and there is no possibility of large pressure drop. The organization, design, user, etc. analyzed the pressure drop when the instrument was put into use. It was believed that the reason for the reduction of the DN40 to DN15 pipeline caused the pressure drop to increase. After communication, the plan of replacing the DN25 mass flowmeter was adopted.
3. Mass flow meter fault solution
When the construction unit replaced the mass flowmeter, after cutting the original pipeline, it was found that there were stones at the front flange of the flowmeter from DN40 to DN15 reducer, blocking the inlet of the flowmeter.
Based on the above analysis, it is found that the main reason for the large pressure drop before and after the flowmeter is that the pressure drop at both ends of the flowmeter increases due to the blockage of stones. After the replacement of the DN25 flowmeter, the nitrogen demand of Company B was met.
Well, that's all for the above situation, I hope I can help you, and if there is more about the flowmeter failure situation, you can exchange details with the editor online at any time.